Checking hours…Mon–Fri 7:30am–5pm · Sat 9am–12pm01302 279234Find parts by applianceTrade account
Ideal Detection Electrode 173024

Ideal

Ideal Detection Electrode 173024

Ideal 173024 detection electrode for Ideal Commercial Imax Plus F80, F120, F160 and F200 boilers, proving flame presence to the control board.

At a glance

  • Part type: Detection electrode
  • Also known as 1179240, N7627
  • This part is fitted to a gas appliance; installation must be carried out by a Gas Safe registered engineer.
Hanicks code
173024
Manufacturer part no.
173024

AvailabilityCall for price

Availability: no longer made. Call us and we'll check for stock.

No longer made: call us

The manufacturer has discontinued this part. Our team will check for remaining stock or a suitable replacement.

01302 279234

Opening hours

Mon–Fri
7:30am–5pm
Sat
9am–12pm
Sun
Closed

Or request a price online

Tell us what you need and we will come back to you. No payment is taken.

Part: 173024 Ideal Detection Electrode 173024

Whichever you would like us to reply to.

Helps us check the part fits.

30-day returns

Unused, in original packaging.

What it is

The Ideal 173024 is a detection electrode used on Ideal Commercial boiler plant. It sits in the combustion path and signals the control board when a flame is established, allowing the burner to run and the gas valve to stay open. It is listed against the Imax Plus range and other Ideal Commercial appliances.

Signs this part needs replacing

  • The boiler fires, then locks out shortly afterwards because no flame signal is returned.
  • Repeated ignition attempts with the burner lighting briefly and then shutting down.
  • Intermittent shutdowns during a demand for heat or hot water.
  • A fault code or lockout pattern pointing to flame detection rather than ignition.
  • Visible damage to the electrode tip, ceramic insulator or lead connection.

Before you order

  • Confirm the appliance model and serial number against the compatibility list, as the electrode is used across several Imax Plus outputs.
  • Check the number on the existing electrode; earlier builds may carry 95250625.
  • Inspect the electrode lead, plug and any sealing washer at the same time, as these are disturbed during replacement.
  • Work on the combustion circuit should be carried out by a competent engineer.
  • This part is fitted to a gas appliance; installation must be carried out by a Gas Safe registered engineer.

Not sure which part?

Tell the parts assistant what it's going into — the appliance make and model, or the GC number off the data badge — and it will check this part is on the fit list.